Mask index
Display description Description
Default UOM Values
Efb09
High alarm High alarm enabling for generic modulating function 1 DISAB. --- DISABLE / ENABLE
High alarm High alarm threshold for generic modulating function 1 0.0 °C … (**)
Delay time High alarm delay for generic modulating function 1 0 s 0…9999
Alarm type Low alarm enabling for generic modulating function 1 LIGHT --- Light / Serious
Efb010
Out upper limit Output upper limit for generic modulating function 1 100.0 % 0…100
Out lower limit Output lower limit for generic modulating function 1 0.0 % 0…100
Enable cutoff Enable cut off function for generic modulating function 1 NO --- NO / SI
Cutoff diff . Cut off diff erential for generic modulating function 1 0.0 °C … (**)
Cutoff hys. Cut off hysteresis for generic modulating function 1 0.0 °C … (**)
Efb20
Low alarm Low alarm enabling for generic modulating function 1 Disab. --- DISABLE / ENABLE
Low alarm Low alarm threshold for generic modulating function 1 0.0 °C … (**)
Delay time Low alarm delay for generic modulating function 1 0 s 0…9999
Alarm type Low alarm type for generic modulating function 1 LIGHT --- Light / Serious
……
Efc05
Gen.alarm 1 Enable generic alarm function 1 management DISAB. --- DISABLE / ENABLE
Gen.alarm 2 Enable generic alarm function 2 management DISAB. --- DISABLE / ENABLE
Efc06
Regulation variable Monitored variable for generic alarm function 1 --- ---
Enable Enabling variable for generic alarm function 1 --- ---
Description Enable description change SKIP --- SKIP / CHANGE
--------------- Description --- ---
Efc07
Alarm type Alarm type for generic alarm function 1 LIGHT --- Light / Serious
Delay time Delay for generic alarm function 1 0 s 0…9999
……
Efd05
Generic Function
Scheduler
Enable generic scheduler function
DISAB. --- DISABLE / ENABLE
Gen.funct.scheduling
connected to global
scheduling
Generic scheduler function considers the same special days and periods
of global scheduler NO --- NO / YES
Efd06 Enable Enabling variable for generic scheduler function --- ---
Efd07
Activ.Time Bands Day of the week --- --- MON, ..., SUN
TB1: --:-- -> --:-- Time band 1 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
……
TB4: --:-- -> --:-- Time band 4 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
Changes Time band changes action
--- ---
---
CONFIRM&SAVE
LOAD PREVIOUS
CLEAR ALL
Copy to Copy settings to other days
0 ---
MONDAY…SUNDAY; MON-FRI;
MON-SAT; SAT&SUN;
ALL DAYS
Efe05
Gen.A Measure Generic analogue input A unit of measure selection °C --- °C; °F; barg; psig; %; ppm -
……